INFINITYPOWER / UPS
DataPower
1–20 kVA
Online double-conversion UPS for IT and sensitive equipment.
Request a quote ↗Original catalogue ↗
Models & part numbers
8 catalogue models. Select a model for its own specification table.
Technical labels and values follow the original English catalogue. “/”, blanks and manufacturer inconsistencies are preserved; confirm final model selection with our team.
DataPower Series — Technical Specifications
PDF · page 7 ↗| Specification | DPS-1000 | DPS-2000 | DPS-3000 |
|---|---|---|---|
| General | |||
| PHASE | Single phase with ground | Single phase with ground | Single phase with ground |
| Capacity(VA/Watts) | 1000/900 | 2000/1800 | 3000/2700 |
| INPUT | |||
| Nominal Voltage | 200/208/220/230/240Vac | 200/208/220/230/240Vac | 200/208/220/230/240Vac |
| Input Voltage Range | 176-264Vac at 100% load | 176-264Vac at 100% load | 176-264Vac at 100% load |
| Frequency Range | 45~55Hz/55~65Hz | 45~55Hz/55~65Hz | 45~55Hz/55~65Hz |
| Power Factor | ≥ 0.99 @Nominal voltage (100% load) | ≥ 0.99 @Nominal voltage (100% load) | ≥ 0.99 @Nominal voltage (100% load) |
| OUTPUT | |||
| Output Voltage | 200/208/220/230/240Vac | 200/208/220/230/240Vac | 200/208/220/230/240Vac |
| Voltage Regulation | ±1% | ±1% | ±1% |
| Frequency Range(Sychronized Range) | 45~55Hz/56~64Hz | 45~55Hz/56~64Hz | 45~55Hz/56~64Hz |
| Frequency Range(Batt.Mode) | 50Hz/60Hz±0.1Hz | 50Hz/60Hz±0.1Hz | 50Hz/60Hz±0.1Hz |
| Current Crest Ratio | 3:1 | 3:1 | 3:1 |
| Harmonic Distortion(THDv) | ≤3% (Linear load) ≤5% (Non-linear load) | ≤3% (Linear load) ≤5% (Non-linear load) | ≤3% (Linear load) ≤5% (Non-linear load) |
| Transfer Time / AC to DC | Zero | Zero | Zero |
| Transfer Time / Inverter to Bypass | 4ms(Typical) | 4ms(Typical) | 4ms(Typical) |
| Waveform | Pure Sinewave | Pure Sinewave | Pure Sinewave |
| EFFICIENCY | |||
| AC Mode | 90% | 91% | 92%Follow the catalogue for more information | ||
| Battery Mode | 95% | 96% | 97%Follow the catalogue for more information | ||
| BATTERY | |||
| Standard Model / Typical Recharge Time | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity |
| Standard Model / Numbers | 2 or 3 | 4 or 6 | 8Follow the catalogue for more information | ||
| Standard Model / Typical Recharge Time | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity | 4 hours recover to 90% capacity |
| Standard Model / Charging Current(max.) | 1.0A | 1.0A | 1.0A |
| Standard Model / Charging Voltage | 27.4Vdc±1% | 54.7Vdc±1% | 82.1Vdc±1%Follow the catalogue for more information | ||
| Long-run Model / Charging Current(max.) | 7A/14A(double board) | 6A/12A(double board)Follow the catalogue for more information | ||
| Long-run Model / Charging Current(max.) | 7A/14A(double board) | 6A/12A(double board)Follow the catalogue for more information | ||
| Long-run Model / Charging Voltage | 41.0Vdc/27.4Vdc ±1% | 54.7Vdc/82.1Vdc/109.4Vdc ±1% | 82.1Vdc/109.4Vdc ±1%Follow the catalogue for more information | ||
| INDICATORS | |||
| LCD | Load level,Battery level,AC mode,Battery mode,Bypass mode,and Fault indicators | Load level,Battery level,AC mode,Battery mode,Bypass mode,and Fault indicators | Load level,Battery level,AC mode,Battery mode,Bypass mode,and Fault indicators |
| ALARM | |||
| Battery mode | Sounding every 4 seconds | Sounding every 4 seconds | Sounding every 4 seconds |
| Low Battery | Sounding every second | Sounding every second | Sounding every second |
| Overload | Sounding twice every second | Sounding twice every second | Sounding twice every second |
| Fault | Continously sounding | Continously sounding | Continously sounding |
| PHYSICAL | |||
| Standard Model / Dimension (D×W×H)mm | 293x144x209 | 460x191x337Follow the catalogue for more information | ||
| Standard Model / Net Weight (kgs) | 10.0 | 21.0 | 26.0Follow the catalogue for more information | ||
| Long-run Model / Dimension (D×W×H)mm | 293x144x209 | 460x191x337Follow the catalogue for more information | ||
| Long-run Model / Net Weight (kgs) | 5.6 | 11.0 | 11.5Follow the catalogue for more information | ||
| ENVIRONMENT | |||
| Humidity | 20~90% RH @ 0~40 oC (Non-condensing) | 20~90% RH @ 0~40 oC (Non-condensing) | 20~90% RH @ 0~40 oC (Non-condensing) |
| Noise level | <50%dB @ 1 Meter | <50%dB @ 1 Meter | <50%dB @ 1 Meter |
| MANAGEMENT | |||
| Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008 Windows® 7/8 Linux,FreeBSD and MAC | Supports Windows® 2000/2003/XP/Vista/2008 Windows® 7/8 Linux,FreeBSD and MAC | Supports Windows® 2000/2003/XP/Vista/2008 Windows® 7/8 Linux,FreeBSD and MAC |
| Optional SNMP | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser | Power management from SNMP manager and web browser |
DataPower Series — Technical Specifications
PDF · page 9 ↗| Specification | DPS-6000 | DPS-10K1-1 |
|---|---|---|
| General | ||
| Capacity (VA/Watts) | 6k / 5.4k | 10k / 9k |
| INPUT | ||
| Nominal voltage | 220/230/240Vac | 220/230/240Vac |
| Operating voltage range | 120~276Vac | 120~276Vac |
| Operating frequency range | 50Hz:45~55Hz;60Hz:54~66Hz(auto sensing) | 50Hz:45~55Hz;60Hz:54~66Hz(auto sensing) |
| Power factor | ≥0.99 | ≥0.99 |
| Bypass voltage range | Max.voltage: 220V: +25%(optional +10%,+15%,+20% ) 230V: +20% (optional +10%,+15%) 240V: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) | Max.voltage: 220V: +25%(optional +10%,+15%,+20% ) 230V: +20% (optional +10%,+15%) 240V: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) |
| ECO range | Same as the bypass | Same as the bypass |
| Harmonic distortion (THDi) | <3%(100% linear load) | <3%(100% linear load) |
| Generator input | Support | Support |
| OUTPUT | ||
| Rated voltage | 220/230/240Vac | 220/230/240Vac |
| Power factor | 0.9 | 0.9 |
| Voltage regulation | ±1% | ±1% |
| Frequency / Line Mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) | ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) |
| Frequency / Bat. Mode | 50/60(±0.1)Hz | 50/60(±0.1)Hz |
| Crest factor | 3:1 | 3:1 |
| Harmonic distortion (THDv) | ≤2% with linear load ≤5% with non-linear load | ≤2% with linear load ≤5% with non-linear load |
| Efficiency | >95% | >95% |
| BATTERY | ||
| Battery voltage | ±96/108/120Vdc (optional) | ±96/108/120Vdc (optional) |
| Capacity (standard unit) | 12V/7Ah/9Ah | 12V/7Ah/9Ah |
| Typical recharge time) | 6~8 hours (to 90% of full capacity) | 6~8 hours (to 90% of full capacity) |
| Charge current | 1A(Standard unit); Long run unit Max.current10A(charge current can be set according to battery capacity installed) | 1A(Standard unit); Long run unit Max.current10A(charge current can be set according to battery capacity installed) |
| SYSTEM FEATURES | ||
| Transfer time | Mains to Battery:0ms; Mains to Bypass:0ms | Mains to Battery:0ms; Mains to Bypass:0ms |
| Overload / Line Mode | Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately | Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately |
| Overload / Bypass Mode | 40A(Breaker) | 60A(Breaker)Follow the catalogue for more information | |
| Short circuit | Hold Whole System | Hold Whole System |
| Overheat | Line Mode: Turn to Bypass; Backup Mode: Shut down UPS immediately | Line Mode: Turn to Bypass; Backup Mode: Shut down UPS immediately |
| Low battery voltage | Alarm and Switch off | Alarm and Switch off |
| Self-diagnostics | Upon Power On and Software Control | Upon Power On and Software Control |
| Battery | Advanced Battery Management | Advanced Battery Management |
| Audible & Visual alarms | Line Failure, Battery Low, Overload, System Fault | Line Failure, Battery Low, Overload, System Fault |
| LED & LCD display | Line Mode, Bat. Mode, Eco Mode, Bypass Mode, Battery Low, Overload & UPS Fault | Line Mode, Bat. Mode, Eco Mode, Bypass Mode, Battery Low, Overload & UPS Fault |
| LCD display | Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage, Inner Temperature & Remaining Battery Backup Time | Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage, Inner Temperature & Remaining Battery Backup Time |
| Comunication interface | RS232,USB,SNMP card(optional), Parallel card(optional), Relay card (optional) | RS232,USB,SNMP card(optional), Parallel card(optional), Relay card (optional) |
| ENVIRONMENTAL | ||
| Operating temperature | 0oC~40oC | 0oC~40oC |
| Storage temperature | -25oC~55oC | -25oC~55oC |
| Humidity range | 0~95% (non-condensing) | 0~95% (non-condensing) |
| Altitude | < 1500m | < 1500m |
| Noise level | <55dB | <55dB |
| PHYSICAL | ||
| Dimension D×W×H (mm) | 460x191x720 | 460x191x720 |
| Net weight (kg) | 54 | 63Follow the catalogue for more information | |
| STANDARDS | ||
| Safety | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 |
| EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
| BATTERY BANK | ||
| Model | DPS-BT Series | DPS-BT Series |
| Battery type& Max.quantity | 2×20pcs/7Ah/(9Ah) | 2×20pcs/7Ah/(9Ah) |
| PHYSICAL OF BATTERY BANK | ||
| Dimensions D×W×H (mm) | 597×250×616 | 597×250×616 |
| Net weight (kg) | 122/134 | 122/134 |
DataPower Series — Technical Specifications
PDF · page 11 ↗| Specification | DPS-10K3-1 | DPS-15K3-1 | DPS-20K3-1 |
|---|---|---|---|
| General | |||
| Capacity(VA/Watts) | 10k / 9k | 15k / 13.5k | 20k / 18k |
| INPUT | |||
| Nominal voltage | 380/400/415Vac;(3Ph+N+PE) | 380/400/415Vac;(3Ph+N+PE) | 380/400/415Vac;(3Ph+N+PE) |
| Operating voltage range | 208~478Vac | 208~478Vac | 208~478Vac |
| Operating frequency range | 50Hz:45~55Hz;60Hz:54~66Hz(auto sensing) | 50Hz:45~55Hz;60Hz:54~66Hz(auto sensing) | 50Hz:45~55Hz;60Hz:54~66Hz(auto sensing) |
| Power factor | ≥0.99 | ≥0.99 | ≥0.99 |
| Bypass voltage range | Max.voltage: 220V: +25%(optional +10%,+15%,+20% ) 230V: +20% (optional +10%,+15%) 240V: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) | Max.voltage: 220V: +25%(optional +10%,+15%,+20% ) 230V: +20% (optional +10%,+15%) 240V: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) | Max.voltage: 220V: +25%(optional +10%,+15%,+20% ) 230V: +20% (optional +10%,+15%) 240V: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) |
| Bypass frequency range | Frequency protection range:±10% | Frequency protection range:±10% | Frequency protection range:±10% |
| ECO range | Same as the bypass | Same as the bypass | Same as the bypass |
| Harmonic distortion (THDi) | <5%(100% linear load) | <5%(100% linear load) | <5%(100% linear load) |
| Generator input | Support | Support | Support |
| OUTPUT | |||
| Rated voltage | 220/230/240Vac | 220/230/240Vac | 220/230/240Vac |
| Power factor | 0.9 | 0.9 | 0.9 |
| Voltage regulation | ±1% | ±1% | ±1% |
| Frequency / Bat. Mode | 50/60(±0.1)Hz | 50/60(±0.1)Hz | 50/60(±0.1)Hz |
| Frequency / Bat. Mode | 50/60(±0.1)Hz | 50/60(±0.1)Hz | 50/60(±0.1)Hz |
| Crest factor | 3:1 | 3:1 | 3:1 |
| Harmonic distortion (THDv) | ≤2% with linear load ≤5% with non-linear load | ≤2% with linear load ≤5% with non-linear load | ≤2% with linear load ≤5% with non-linear load |
| Efficiency | 95% | 95.5%Follow the catalogue for more information | ||
| BATTERY | |||
| Battery voltage | ±96/108/120Vdc (optional) | ±96/108/120Vdc (optional) | ±96/108/120Vdc (optional) |
| Capacity (standard unit) | 12V/7Ah/9Ah | 12V/7Ah/9Ah | 12V/7Ah/9Ah |
| Typical recharge time | 6~8 hours (to 90% of full capacity) | 6~8 hours (to 90% of full capacity) | 6~8 hours (to 90% of full capacity) |
| Charge current | 1A(10kVA Standard unit) ; Max.current 10A(Long run unit) | 1A(10kVA Standard unit) ; Max.current 10A(Long run unit) | 1A(10kVA Standard unit) ; Max.current 10A(Long run unit) |
| SYSTEM FEATURES | |||
| Transfer time | Mains to Battery:0ms; Mains to Bypass:0ms | Mains to Battery:0ms; Mains to Bypass:0ms | Mains to Battery:0ms; Mains to Bypass:0ms |
| Overload / Line Mode | Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately | Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately | Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately |
| Overload / Bypass Mode | 63A(Breaker) | 100A(Breaker) | 125A(Breaker)Follow the catalogue for more information | ||
| Short circuit | Hold Whole System | Hold Whole System | Hold Whole System |
| Overheat | Line Mode: Turn to Bypass; Bat. Mode: Shut down UPS immediately | Line Mode: Turn to Bypass; Bat. Mode: Shut down UPS immediately | Line Mode: Turn to Bypass; Bat. Mode: Shut down UPS immediately |
| Low battery voltage | Alarm and Switch off | Alarm and Switch off | Alarm and Switch off |
| Self-diagnostics | Upon Power On and Software Control | Upon Power On and Software Control | Upon Power On and Software Control |
| Battery | Advanced Battery Management | Advanced Battery Management | Advanced Battery Management |
| Audible & Visual alarms | Line Failure, Battery Low, Overload, System Fault | Line Failure, Battery Low, Overload, System Fault | Line Failure, Battery Low, Overload, System Fault |
| LED & LCD display | Line Mode, Bat. Mode, Eco Mode, Bypass Mode, Battery Low, Overload & UPS Fault | Line Mode, Bat. Mode, Eco Mode, Bypass Mode, Battery Low, Overload & UPS Fault | Line Mode, Bat. Mode, Eco Mode, Bypass Mode, Battery Low, Overload & UPS Fault |
| LCD display | Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage, Inner Temperature & Remaining Battery Backup Time | Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage, Inner Temperature & Remaining Battery Backup Time | Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage, Inner Temperature & Remaining Battery Backup Time |
| Communication interface | RS232,USB,SNMP card(optional), Parallel board(optional), Relay card (optional) | RS232,USB,SNMP card(optional), Parallel board(optional), Relay card (optional) | RS232,USB,SNMP card(optional), Parallel board(optional), Relay card (optional) |
| ENVIRONMENTAL | |||
| Operating temperature | 0oC~40oC | 0oC~40oC | 0oC~40oC |
| Storage temperature | -25oC~55oC | -25oC~55oC | -25oC~55oC |
| Humidity range | 0~95% (non-condensing) | 0~95% (non-condensing) | 0~95% (non-condensing) |
| Altitude | < 1500m | < 1500m | < 1500m |
| Noise level | <55dB | <58dBFollow the catalogue for more information | ||
| PHYSICAL | |||
| Dimension D×W×H (mm) | 597×250×655(S)/502×250×616(H) | 502×250×616Follow the catalogue for more information | ||
| Net weight (kg) | 76(S)/35 (H) | 45 | 46Follow the catalogue for more information | ||
| STANDARDS | |||
| Safety | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 |
| EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
| BATTERY BANK | |||
| Model | DPS-BT Series | DPS-BT Series | DPS-BT Series |
| Battery type& Max.quantity | 2×20pcs/7Ah(9Ah) | 2×20pcs/7Ah(9Ah) | 2×20pcs/7Ah(9Ah) |
| PHYSICAL OF BATTERY BANK | |||
| Dimensions D×W×H (mm) | 597×250×616 | 597×250×616 | 597×250×616 |
| Net weight (kg) | 122/134 | 122/134 | 122/134 |
Catalogue features and options · PDF 6
Data Power Series
--------------------------------------
ONLINE DOUBLE CONVERSION UPS
1kVA To 3kVA (0.9 PF) Tower
Features
• High power density
• Online double conversion with full digital control
• Wide input voltage range: 110~300Vac
• Input power factor 0.99 with PFC
3 kinds of LCD can be selected
• Selectable output voltage: 208/220/230/240Vac
• Smart charger design for optimized battery
performance
• Maximum charging current can be expanded to 12A
(Long run unit)
Colourful Blue LCD Advanced
• Emergency power off function (EPO)
LCD Touch Screen
• ECO mode operation for energy saving
• Generator compatible
• Cold start
• Intelligent fan speed regulation
• Load segment settable (Optional)
• Versatile LCD human-computer interface
• Multiple communication interface: RS232 (USB/
Battery Cabinet Optimized Battery
EPO/
(Optional) Configuration 7/9Ah
• Dry contact card/SNMP card optional)
• Multiple protection function: short-circuit, overload,
overheat, battery overcharge and overdischarge,
output low voltage and fan fault alarm
SNMP card
Dry contact
card
Optional socket Rear Panel
06
--------------------------------------
ONLINE DOUBLE CONVERSION UPS
1kVA To 3kVA (0.9 PF) Tower
Features
• High power density
• Online double conversion with full digital control
• Wide input voltage range: 110~300Vac
• Input power factor 0.99 with PFC
3 kinds of LCD can be selected
• Selectable output voltage: 208/220/230/240Vac
• Smart charger design for optimized battery
performance
• Maximum charging current can be expanded to 12A
(Long run unit)
Colourful Blue LCD Advanced
• Emergency power off function (EPO)
LCD Touch Screen
• ECO mode operation for energy saving
• Generator compatible
• Cold start
• Intelligent fan speed regulation
• Load segment settable (Optional)
• Versatile LCD human-computer interface
• Multiple communication interface: RS232 (USB/
Battery Cabinet Optimized Battery
EPO/
(Optional) Configuration 7/9Ah
• Dry contact card/SNMP card optional)
• Multiple protection function: short-circuit, overload,
overheat, battery overcharge and overdischarge,
output low voltage and fan fault alarm
SNMP card
Dry contact
card
Optional socket Rear Panel
06
Catalogue features and options · PDF 8
Data Power Series
--------------------------------------
ONLINE DOUBLE CONVERSION UPS
6kVA To 10kVA (0.9 PF)
Single Phase input/output (1:1) Tower
Features
• N+X parallel redundancy, support maximum 4
units in parallel
• Online double conversion with full digital
control
• 3-level inverter topology, the efficiency can be
5 Kinds of LCD can be selected
up to 95.5%
• Wide input voltage range: 110~300Vac
• Dual input source (Optional)
• Generator compatible
• Supporting customized shared battery banks
Battery Cabinet Optimized Battery
for parallel system (The battery banks should
(Optional) Configuration
be configured with neutral line)
7/9Ah
• Dual Intelligent card slot for touch screen
version
• (Segment LCD optional)
• Maximum charging current up to 15A Dry contact card
• Cold start function
• Dry contact port optional (4 pins input and 4
pins output)
• Intelligent fan speed regulation
SNMP card
• Low noise design, less than 45dB for 6kVA
• Multiple protection function: short-circuit,
overload, overheat, battery overcharge and
overdischarge, output low voltage and fan
fault alarm
08
--------------------------------------
ONLINE DOUBLE CONVERSION UPS
6kVA To 10kVA (0.9 PF)
Single Phase input/output (1:1) Tower
Features
• N+X parallel redundancy, support maximum 4
units in parallel
• Online double conversion with full digital
control
• 3-level inverter topology, the efficiency can be
5 Kinds of LCD can be selected
up to 95.5%
• Wide input voltage range: 110~300Vac
• Dual input source (Optional)
• Generator compatible
• Supporting customized shared battery banks
Battery Cabinet Optimized Battery
for parallel system (The battery banks should
(Optional) Configuration
be configured with neutral line)
7/9Ah
• Dual Intelligent card slot for touch screen
version
• (Segment LCD optional)
• Maximum charging current up to 15A Dry contact card
• Cold start function
• Dry contact port optional (4 pins input and 4
pins output)
• Intelligent fan speed regulation
SNMP card
• Low noise design, less than 45dB for 6kVA
• Multiple protection function: short-circuit,
overload, overheat, battery overcharge and
overdischarge, output low voltage and fan
fault alarm
08
Catalogue features and options · PDF 10
Data Power Series
--------------------------------------
ONLINE DOUBLE CONVERSION UPS
10kVA To 20kVA (0.9 PF)
3 PH input/1 PH output (3:1) Tower
Features
• N+X parallel redundancy
• Online double conversion with DSP control
• Input current harmonic: <5%
• Optimization battery group, the quantity of
battery: 16/18/20 pieces (optional)
• factor is changed when selection different
battery quantity 16pc:0.7PF;18PCS:0.8PF;20P Control Panel
CS:0.9PF
• Wide input voltage range: 208~478Vac
• Wide input frequency range(50Hz: 45~55Hz /
60Hz: 54~66Hz)
• Support generator input Relay card
• Support economic(ECO) operation mode
• Self-testing when UPS startup
• Options: SNMP card/Relay card/ Parallel
board
• Cold start SNMP
Parallel board
Battery Cabinets
(Optional) Rear Panel
10
--------------------------------------
ONLINE DOUBLE CONVERSION UPS
10kVA To 20kVA (0.9 PF)
3 PH input/1 PH output (3:1) Tower
Features
• N+X parallel redundancy
• Online double conversion with DSP control
• Input current harmonic: <5%
• Optimization battery group, the quantity of
battery: 16/18/20 pieces (optional)
• factor is changed when selection different
battery quantity 16pc:0.7PF;18PCS:0.8PF;20P Control Panel
CS:0.9PF
• Wide input voltage range: 208~478Vac
• Wide input frequency range(50Hz: 45~55Hz /
60Hz: 54~66Hz)
• Support generator input Relay card
• Support economic(ECO) operation mode
• Self-testing when UPS startup
• Options: SNMP card/Relay card/ Parallel
board
• Cold start SNMP
Parallel board
Battery Cabinets
(Optional) Rear Panel
10