INFINITYPOWER / UPS

PowerExpand

10–1,560 kVA

Modular UPS architecture designed around growing power needs.

Request a quote ↗Original catalogue ↗
PowerExpand
Representative family configuration from the catalogue.

Models & part numbers

3 catalogue models. Select a model for its own specification table.

Technical labels and values follow the original English catalogue. “/”, blanks and manufacturer inconsistencies are preserved; confirm final model selection with our team.

PowerExpand Series — Technical Specifications

PDF · page 29 ↗
PowerExpand Series — Technical Specifications
SpecificationPEX10-60KVAPEX10-100KVAPEX10-200KVA
General
Capacity(VA/Watts) / HPM module10k / 9k, 20k / 18k10k / 9k, 20k / 18k10k / 9k, 20k / 18k
Capacity(VA/Watts) / HPM module10k / 9k, 20k / 18k10k / 9k, 20k / 18k10k / 9k, 20k / 18k
INPUT
Nominal voltage380/400/415Vac, (3Ph+N+PE)380/400/415Vac, (3Ph+N+PE)380/400/415Vac, (3Ph+N+PE)
Operating voltage range208~478Vac208~478Vac208~478Vac
Operating frequency range40~70Hz40~70Hz40~70Hz
Power factor≥0.99≥0.99≥0.99
Bypass voltage rangeMax.voltage: 220v +25%(optional +10%,+15%,+20% ) 230v 20% (optional +10%,+15%) 240v 15%(optional +10%) Min. voltage: -45% (optional -20%,-30%) Frequency protection range: ±10%Max.voltage: 220v +25%(optional +10%,+15%,+20% ) 230v 20% (optional +10%,+15%) 240v 15%(optional +10%) Min. voltage: -45% (optional -20%,-30%) Frequency protection range: ±10%Max.voltage: 220v +25%(optional +10%,+15%,+20% ) 230v 20% (optional +10%,+15%) 240v 15%(optional +10%) Min. voltage: -45% (optional -20%,-30%) Frequency protection range: ±10%
Harmonic distortion (THDi)2%(100% nonlinear load)2%(100% nonlinear load)2%(100% nonlinear load)
Generator inputSupportSupportSupport
OUTPUT
Output voltage380/400/415Vac, (3Ph+N+PE)380/400/415Vac, (3Ph+N+PE)380/400/415Vac, (3Ph+N+PE)
Voltage regulation±1%±1%±1%
Power factor0.90.90.9
Output frequency1.Line Mode: ±1%,±2%,±4%,±5%,±10% of the rated frequency (optional) 2.Battery Mode: (50/60±0.1%)Hz1.Line Mode: ±1%,±2%,±4%,±5%,±10% of the rated frequency (optional) 2.Battery Mode: (50/60±0.1%)Hz1.Line Mode: ±1%,±2%,±4%,±5%,±10% of the rated frequency (optional) 2.Battery Mode: (50/60±0.1%)Hz
Crest factor3:13:13:1
Harmonic distortion (THDv)≤2% with linear load ≤5% with non linear load≤2% with linear load ≤5% with non linear load≤2% with linear load ≤5% with non linear load
Efficiency96.5%96.5%96.5%
BATTERY
Battery voltage±192\±204\±216\±228\±240Vdc; battery quantity(optional)±192\±204\±216\±228\±240Vdc; battery quantity(optional)±192\±204\±216\±228\±240Vdc; battery quantity(optional)
Charge current / UPS cabinet18A (Max) | 30A (Max) | 60A (Max.)Follow the catalogue for more information
Charge current / HPM module6A (Max.) (charge current can be set according to battery capacity installed)6A (Max.) (charge current can be set according to battery capacity installed)6A (Max.) (charge current can be set according to battery capacity installed)
Backup timeDepends on the capacity of external batteriesDepends on the capacity of external batteriesDepends on the capacity of external batteries
SYSTEM FEATURES
Transfer timeUtility to Battery : 0ms; Utility to bypass: 0msUtility to Battery : 0ms; Utility to bypass: 0msUtility to Battery : 0ms; Utility to bypass: 0ms
Overload / Bat. ModeLoad≤110%: last 10min,≤125%: last 1min, ≤150%: last 1S,≥150% shut down UPS immediatelyLoad≤110%: last 10min,≤125%: last 1min, ≤150%: last 1S,≥150% shut down UPS immediatelyLoad≤110%: last 10min,≤125%: last 1min, ≤150%: last 1S,≥150% shut down UPS immediately
Overload / Bat. ModeLoad≤110%: last 10min,≤125%: last 1min, ≤150%: last 1S,≥150% shut down UPS immediatelyLoad≤110%: last 10min,≤125%: last 1min, ≤150%: last 1S,≥150% shut down UPS immediatelyLoad≤110%: last 10min,≤125%: last 1min, ≤150%: last 1S,≥150% shut down UPS immediately
Overload / Bypass ModeBreaker (10kVA: 20A / 20kVA:40A)Breaker (10kVA: 20A / 20kVA:40A)Breaker (10kVA: 20A / 20kVA:40A)
Short circuitHold whole systemHold whole systemHold whole system
Nose suppressionComplies with EN62040-2Complies with EN62040-2Complies with EN62040-2
Communication interface1. UPS cabinet : RS232, RS485, Dry Contact, Intelligent slot x 2(SNMP card,Relay card optional) 2. PEX series UPS module: RS2321. UPS cabinet : RS232, RS485, Dry Contact, Intelligent slot x 2(SNMP card,Relay card optional) 2. PEX series UPS module: RS2321. UPS cabinet : RS232, RS485, Dry Contact, Intelligent slot x 2(SNMP card,Relay card optional) 2. PEX series UPS module: RS232
ENVIRONMENTAL
Operating temperature0oC~40oC0oC~40oC0oC~40oC
Storage temperature-25oC~55oC-25oC~55oC-25oC~55oC
Humidity range0~95% (non-condensing)0~95% (non-condensing)0~95% (non-condensing)
Altitude<1500m<1500m<1500m
Noise level<65dB<65dB<65dB
PHYSICAL
Dimension D×W×H (mm) / HPM module443x580x131 (3U)443x580x131 (3U)443x580x131 (3U)
Dimension D×W×H (mm) / HPM module443x580x131 (3U)443x580x131 (3U)443x580x131 (3U)
Net weight (kg) / UPS cabinet149 | 152 | 290Follow the catalogue for more information
Net weight (kg) / UPS cabinet10kVA/26; 20kVA/3110kVA/26; 20kVA/3110kVA/26; 20kVA/31
STANDARDS
SafetyIEC/EN62040-1,IEC/EN60950-1IEC/EN62040-1,IEC/EN60950-1IEC/EN62040-1,IEC/EN60950-1
EMCIEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
Catalogue features and options · PDF 28
Power Expand Series
--------------------------------------
More Power, More Effciency, Less Space..
Hot Swappable Modular UPS..
PAY AS YOU GROW
10~1560kVA
PEX-PM10kVA | PEX-PM20kVA Power Module
PEX10-30kVA | PEX20-60kVA
PEX10-50kVA | PEX20-100kVA
PEX10-100kVA | PEX20-200kVA
Features
• Hot swap batteries and modules
• High frequency and double conversion
on-line technology
• Advanced PFC technology
• 3U frame, rack-mounted and tower convertible
UPS Cabinet Module Control
• EPO function
Control Panel Panel
• Wide input voltage range
• Fully digitized microprocessor control
• Parallel redundancy
single module(3U)
• Advanced battery management
• Lightning and surge protection, short circuit
and overload protection
• Multilingual LCD and LED display
10KVA / 20KVA 3:3 phase
• EMI/RFI noise filter
• Smart RS232 communication with monitoring
software
• Optional SNMP card slot
Battery Cabinets 3 U Battery Box
(Optional) Optional
28