INFINITYPOWER / MODEL & PART NUMBER
DPPS-10K3-1
DataPower+ · Flexible online power protection in multiple input configurations.
Enquire about this model ↗Technical labels and values follow the original English catalogue. “/”, blanks and manufacturer inconsistencies are preserved; confirm final model selection with our team.
DataPower+ Series — Technical Specifications
PDF · page 17 ↗| Specification | DPPS-10K3-1 |
|---|---|
| General | |
| Capacity(VA/Watts) | 10k / 9k |
| INPUT | |
| Nominal Voltage | 380/400/415Vac(3Ph+N+PE) or 220/230/240Vac(L+N+PE) |
| Operating voltage range | 208~478Vac or 120Vac~276Vac |
| Operating frequency range | 50Hz:45~55Hz;60Hz:54~66Hz(auto sensing) |
| Power factor | ≥0.99 |
| Bypass voltage range | Max. voltage: 220V: +25%(optional +10%,+15%,+20% ) 230V: +20% (optional +10%,+15%), 240V: +15% (optional +10%) Min. voltage: -45% (optional -20%,-30%) |
| Bypass frequency range | Frequency protection range:±10 |
| ECO range | Same as bypass |
| Harmonic distortion (THDi) | ≤5%(100% linear load) |
| Generator input | Support |
| OUTPUT | |
| Output voltage | 220/230/240Vac |
| Power factor | 0.9 |
| Voltage regulation | ±1% |
| Frequency / Bat. Mode | 50/60(±0.1)Hz |
| Frequency / Bat. Mode | 50/60(±0.1)Hz |
| Crest factor | 3:1 |
| Harmonic distortion (THDv) | ≤2% with linear load, ≤5% with non linear load |
| Efficiency | >95% |
| BATTERY | |
| Battery voltage | ±96/108/120Vdc (optional) |
| Backup time | Long run unit depends on the capacity of external batteries Estimated remaining time displayed on the LCD |
| Typical recharge time | 6~8 hours (to 90% of full capacity) |
| Charge current | Maximum Current 10A; charge current can be set according to battery capacity installed |
| SYSTEM FEATURES | |
| Transfer time | Mains to Battery:0ms; Mains to Bypass:0ms |
| Overload / Line Mode | Load≤110%:60min; ≤125%:last 10min; ≤150%:last 1min;>150% turn to bypass mode |
| Overload / Bypass Mode | 60A(Input breaker) |
| Short Circuit | Hold Whole System |
| Overheat | Line Mode: Turn to Bypass; Backup Mode: Shut down UPS immediately |
| Low battery voltage | Alarm and Switch off |
| Self-diagnostics | Upon Power On and Software Control |
| Battery | Advanced Battery Management |
| Audible & Visual alarms | Line Failure, Battery Low, Overload, System Fault |
| Status LED & LCD display | Line Mode, Bat. Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault |
| Reading on the LCD display | Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage, Inner Temperature & Remaining Battery Backup Time |
| Comunication interface | RS232,USB,SNMP card(optional), Relay card (optional) |
| ENVIRONMENTAL | |
| Operating temperature | 0oC~40oC |
| Storage temperature | -25oC~55oC |
| Humidity range | 0~95% (non condensing) |
| Altitude | <1500m |
| Noise level | <55dB |
| PHYSICAL | |
| Dimension W×H×D (mm) | 580×443×131(3U) |
| Net Weight (kg) | 25 |
| STANDARDS | |
| Safety | IEC/EN62040-1,IEC/EN60950-1 |
| EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
| BATTERY BANK | |
| Model | DPPS-BR Series |
| Battery type& Max.quantity | 9Ah×20 |
| PHYSICAL OF BATTERY BANK | |
| Dimensions D×W×H (mm) | 720×443×131(3U) |