INFINITYPOWER · İSTANBUL, TÜRKİYE+90 212 689 86 84
← DataPower+

INFINITYPOWER / MODEL & PART NUMBER

DPPS-6000

DataPower+ · Flexible online power protection in multiple input configurations.

Enquire about this model ↗

Technical labels and values follow the original English catalogue. “/”, blanks and manufacturer inconsistencies are preserved; confirm final model selection with our team.

DataPower+ Series — Technical Specifications

PDF · page 15 ↗
DataPower+ Series — Technical Specifications
SpecificationDPPS-6000
General
Capacity(VA/Watts)6k / 5.4k
INPUT
Nominal Voltage220/230/240Vac(L+N+PE)
Operating voltage range110~300 (110~300@50% load/176~300@100% load)
Operating frequency range45~55Hz/54~66Hz±0.5Hz
Power factor≥0.99
Bypass voltage range220V: +25%(optional +10%,+15%,+20% ) 230: +20% (optional +10%,+15%) 240: +15% (optional +10%) Min. voltage: -45% (optional -20%,-30%)
ECO rangeSame as bypass
Harmonic distortion (THDi)≤3%(100% linear load)
Generator inputSupport
OUTPUT
Output voltage220/230/240Vac
Power factor0.9
Voltage regulation±2%
Frequency / Bat. Mode50/60 (±0.1)Hz
Frequency / Bat. Mode50/60 (±0.1)Hz
Crest factor3:1
Harmonic distortion (THDv)≤2% with linear load ≤5% with non linear load
WaveformPure Sinewave
Efficiency>95%
BATTERY
Battery voltageOptional Voltage: ±96/±108/±120Vdc VRLA or LI-ion
Typical recharge time6~8 hours (to 90% of full capacity)
Charge currentMaximum Current 6A; charge current can be set according to battery capacity installed.
SYSTEM FEATURES
Transfer timeUtility to Battery : 0ms; Utility to bypass: 0ms
Overload / Line ModeLoad≤110%: last 60min; ≤125%: last 10min; ≤150%: last 1S;>150% turn to bypass mode
Overload / Bypass Mode40A(Input breaker)
Short CircuitHold Whole System
OverheatLine Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltageAlarm and Switch off
Self-diagnosticsUpon Power On and Software Control
EPO (optional)Shut down UPS immediately
BatteryAdvanced Battery Management
Noise SuppressionComplies with EN62040-2
Audible & Visual alarmsLine Failure, Battery Low, Overload, System Fault
Status LED & LCD displayLine Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault
Reading on the LCD displayInput Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage, Inner Temperature & Remaining Battery Backup Time
Comunication interfaceUSB,RS232,Parallel Port, SNMPcard/Relay card (optional)
ENVIRONMENTAL
Operating temperature0~40oC
Storage temperature-25~55oC
Humidity range0~95% (non condensing)
Altitude<1500m
Noise level<45
PHYSICAL
Dimension W×H×D (mm)440×621.5×86.5 (2U) | 440×621.5×175 (4U)Follow the catalogue for more information
Net Weight (kg)15 | 57/65 | 17 | 67Follow the catalogue for more information
STANDARDS
SafetyIEC/EN62040-1,IEC/EN60950-1
EMCIEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8