INFINITYPOWER · İSTANBUL, TÜRKİYE+90 212 689 86 84

INFINITYPOWER / UPS

PowerExpand Plus

50–1,200 kVA

Modular power infrastructure for larger installations.

Request a quote ↗Original catalogue ↗
PowerExpand Plus
Representative family configuration from the catalogue.

Models & part numbers

2 catalogue models. Select a model for its own specification table.

Technical labels and values follow the original English catalogue. “/”, blanks and manufacturer inconsistencies are preserved; confirm final model selection with our team.

PowerExpand Plus Series — Technical Specifications

PDF · page 31 ↗
PowerExpand Plus Series — Technical Specifications
SpecificationPEXP50PEXP60
General
Capacity(VA/Watts) / HPM module5060
Capacity(VA/Watts) / HPM module5060
Capacity(VA/Watts) / Max. Number4/6/8/10/12/16/205/10/14/18/20
Max. Parallel Number88
INPUT
Nominal voltage380/400/415Vac, (3Ph+N+PE)380/400/415Vac, (3Ph+N+PE)
Operating voltage range138~305 for 40% load; 305~485 for 100% load138~305 for 40% load; 305~485 for 100% load
Power factor≥0.99≥0.99
Harmonic Distortion (THDi)≤3% (100% Linear load)≤3% (100% Linear load)
Bypass voltage rangeMax. voltage: 220: +25% (Optional+10%, +15%, +20%) 230: +20% (Optional+10%, +15%), 240: +15% (Optional+10%) Min. voltage: -45% (Optional-10%, -15% -20%, -30%)Max. voltage: 220: +25% (Optional+10%, +15%, +20%) 230: +20% (Optional+10%, +15%), 240: +15% (Optional+10%) Min. voltage: -45% (Optional-10%, -15% -20%, -30%)
Bypass Frequency Range (Hz)50/60±10%50/60±10%
OUTPUT
Nominal Voltage (Vac)380/400/415 (3Ph+N+PE)380/400/415 (3Ph+N+PE)
Voltage Regulation±1%±1%
Output Frequency (Hz)Line mode: Synchronize with input, when the input frequency >±10% (±1%/±2%/±4%/±5% optional), output 50/60 (±0.1z); Bat. mode: (50/60±0.1%)Line mode: Synchronize with input, when the input frequency >±10% (±1%/±2%/±4%/±5% optional), output 50/60 (±0.1z); Bat. mode: (50/60±0.1%)
Crest Factor3:13:1
Harmonic Distortion (THDv)≤2% with linear load; ≤4% with nonlinear load≤2% with linear load; ≤4% with nonlinear load
Overload / Bypass mode30oC: 135% for long term; 40oC: 125% for long term; >1000%, 100ms30oC: 135% for long term; 40oC: 125% for long term; >1000%, 100ms
Overload / Bypass mode30oC: 135% for long term; 40oC: 125% for long term; >1000%, 100ms30oC: 135% for long term; 40oC: 125% for long term; >1000%, 100ms
EFFICIENCY*
AC ModeUp to 96%Up to 96%
ECO ModeUp to 99%Up to 99%
HECO ModeUp to 99%Up to 99%
BATTERY
Battery TypeVRLA/Li-ionVRLA/Li-ion
Battery Voltage (Vdc)360~600360~600
Charging Current (Max.)(A)2020
MANAGEMENT
LCD DisplayLine voltage, Bypass Mode, Battery Low, Battery Fault, Overload & UPS FaultLine voltage, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault
AlarmLine Failure, Battery Low, Overload, System FaultLine Failure, Battery Low, Overload, System Fault
Communication PortsRS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card (Optional), SNMP card (Optional), Battery temperature sensor (Optional)RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card (Optional), SNMP card (Optional), Battery temperature sensor (Optional)
SYSTEM FEATURES
OverheatLine Mode: Switch to Bypass; Backup Mode: Shut down UPS immediatelyLine Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Self-diagnosticsUpon Power On and Software ControlUpon Power On and Software Control
Generator InputSupportSupport
EPOShut down UPS immediatelyShut down UPS immediately
ENVIRONMENTAL
Operating Temperature (oC)0~400~40
Storage Temperature (oC)-25~55-25~55
Humidity Range0~95% (Non condensing)0~95% (Non condensing)
Altitude (m)<1000, derating required when >1000<1000, derating required when >1000
Noise Level (dB)Not specified<73
PHYSICAL
Dimension WxDxH (mm) / UPS Cabinet (S/F)200/300/400kVA: 600×850×2000 500/600kVA: 1200×850×2000 800/1000kVA: 2000×850×2000300kVA: 600×850×2000; 600kVA: 1200×850×2000 840/1080kVA: 2000×850×2000; 1200kVA: 2200×850×2000
Dimension WxDxH (mm) / Power Module440×620×130440×620×130
Weight (kg) / UPS Cabinet200kVA: 270; 300kVA: 290; 400kVA: 310; 500kVA: 650; 600kVA: 720; 800kVA: 980; 1000kVA: 1080300kVA: 290; 600kVA: 720; 800kVA: 980; 1080kVA: 1080; 1200kVA: 1200
Weight (kg) / Power Module3435
STANDARDS
SafetyIEC/EN 62040-1, IEC/EN 62477-1IEC/EN 62040-1, IEC/EN 62477-1
EMCIEC/EN 62040-2 (IEC 61000-2-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11)IEC/EN 62040-2 (IEC 61000-2-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11)
PerformanceIEC 62040-3: 2021, EN IEC 62040-3: 2021IEC 62040-3: 2021, EN IEC 62040-3: 2021
Catalogue features and options · PDF 30
power expand plus series
Power range: 50~1200kVA (3-Level PF: 1.0)
Mode: 3 phase input and 3 phase output
Module: 50/60kVA
Modular Design VRLA & Lithium Battery Supportable
• All units adopt modular design, including power • Compatible with VRLA or lithium battery
module, bypass module, monitoring module, can be
easily integrated. Parallel Redundancy Function
• Power module, Bypass module, Monitoring module,
• Support parallel expanded operation: maximum is 8
ECU control module, all these modules are hot-
units
swappable
• Support sharing batteries for the UPS in parallel
High Reliability
Strong Load Capability*
• Wide input voltage range, line voltage range is 138-
485V, UPS will derate to 40% when input voltage is • Output power factor is 1.0, UPS can supply power to
below 305V. 100% unbalanced load.
• UPS adopts multiple digital bus and redundancy
• High adaptability for load, it can connect full inductive
parallel control system, making sure the whole
load or capacitive load.
system keep online if any single circuit fail.
• The UPS will keep on single or parallel working, if any Intelligent Management
module fail.
• With 7 inches (Standard) and 10 inches (Optional)
• Thickened conformal coating, applicable for harsh
colorful touch LCD screen.
environment such as high heat, high humidity, dust.
• Support recording and exporting history logs and
Green and Power Saving
fault logs.
• High input power factor, it is up to 0.99. • Support SNMP, RS232, RS485, BMS, Dry contact
• 3-level topology design, online efficiency up to 96% interface.
• THDi<3% (100% linear load). • Support upgrading FW&SW on line (In bypass mode)
• The UPS will work in sleeping mode when the load is
• EPO & REPO function.
very small (Settable).
Compatible with Generator
LBS Function
• Power Walk In function, it can reduce the start current
• LBS function can realize 2 independent UPS system
impact to system, and it can reduce the capacity of
work in synchronization, and it enhances the
generator
reliability of the system.
30