PowerExpand Plus Series — Technical Specifications

PDF · page 31 ↗
PowerExpand Plus Series — Technical Specifications
SpecificationPEXP60
General
Capacity(VA/Watts) / HPM module60
Capacity(VA/Watts) / HPM module60
Capacity(VA/Watts) / Max. Number5/10/14/18/20
Max. Parallel Number8
INPUT
Nominal voltage380/400/415Vac, (3Ph+N+PE)
Operating voltage range138~305 for 40% load; 305~485 for 100% load
Power factor≥0.99
Harmonic Distortion (THDi)≤3% (100% Linear load)
Bypass voltage rangeMax. voltage: 220: +25% (Optional+10%, +15%, +20%) 230: +20% (Optional+10%, +15%), 240: +15% (Optional+10%) Min. voltage: -45% (Optional-10%, -15% -20%, -30%)
Bypass Frequency Range (Hz)50/60±10%
OUTPUT
Nominal Voltage (Vac)380/400/415 (3Ph+N+PE)
Voltage Regulation±1%
Output Frequency (Hz)Line mode: Synchronize with input, when the input frequency >±10% (±1%/±2%/±4%/±5% optional), output 50/60 (±0.1z); Bat. mode: (50/60±0.1%)
Crest Factor3:1
Harmonic Distortion (THDv)≤2% with linear load; ≤4% with nonlinear load
Overload / Bypass mode30oC: 135% for long term; 40oC: 125% for long term; >1000%, 100ms
Overload / Bypass mode30oC: 135% for long term; 40oC: 125% for long term; >1000%, 100ms
EFFICIENCY*
AC ModeUp to 96%
ECO ModeUp to 99%
HECO ModeUp to 99%
BATTERY
Battery TypeVRLA/Li-ion
Battery Voltage (Vdc)360~600
Charging Current (Max.)(A)20
MANAGEMENT
LCD DisplayLine voltage, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault
AlarmLine Failure, Battery Low, Overload, System Fault
Communication PortsRS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card (Optional), SNMP card (Optional), Battery temperature sensor (Optional)
SYSTEM FEATURES
OverheatLine Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Self-diagnosticsUpon Power On and Software Control
Generator InputSupport
EPOShut down UPS immediately
ENVIRONMENTAL
Operating Temperature (oC)0~40
Storage Temperature (oC)-25~55
Humidity Range0~95% (Non condensing)
Altitude (m)<1000, derating required when >1000
Noise Level (dB)<73
PHYSICAL
Dimension WxDxH (mm) / UPS Cabinet (S/F)300kVA: 600×850×2000; 600kVA: 1200×850×2000 840/1080kVA: 2000×850×2000; 1200kVA: 2200×850×2000
Dimension WxDxH (mm) / Power Module440×620×130
Weight (kg) / UPS Cabinet300kVA: 290; 600kVA: 720; 800kVA: 980; 1080kVA: 1080; 1200kVA: 1200
Weight (kg) / Power Module35
STANDARDS
SafetyIEC/EN 62040-1, IEC/EN 62477-1
EMCIEC/EN 62040-2 (IEC 61000-2-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11)
PerformanceIEC 62040-3: 2021, EN IEC 62040-3: 2021