DPS-10K1-1
DataPower · BT ve hassas ekipman için online çift çevrim UPS.
Bu model hakkında bilgi alın ↗Teknik etiketler ve değerler orijinal İngilizce kataloğu izler. “/”, boş değerler ve üretici tutarsızlıkları korunmuştur; nihai model seçimini ekibimizle doğrulayın.
DataPower Series — Technical Specifications
PDF · sayfa 9 ↗| Teknik özellik | DPS-10K1-1 |
|---|---|
| General | |
| Capacity (VA/Watts) | 10k / 9k |
| INPUT | |
| Nominal voltage | 220/230/240Vac |
| Operating voltage range | 120~276Vac |
| Operating frequency range | 50Hz:45~55Hz;60Hz:54~66Hz(auto sensing) |
| Power factor | ≥0.99 |
| Bypass voltage range | Max.voltage: 220V: +25%(optional +10%,+15%,+20% ) 230V: +20% (optional +10%,+15%) 240V: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%) |
| ECO range | Same as the bypass |
| Harmonic distortion (THDi) | <3%(100% linear load) |
| Generator input | Support |
| OUTPUT | |
| Rated voltage | 220/230/240Vac |
| Power factor | 0.9 |
| Voltage regulation | ±1% |
| Frequency / Line Mode | ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional) |
| Frequency / Bat. Mode | 50/60(±0.1)Hz |
| Crest factor | 3:1 |
| Harmonic distortion (THDv) | ≤2% with linear load ≤5% with non-linear load |
| Efficiency | >95% |
| BATTERY | |
| Battery voltage | ±96/108/120Vdc (optional) |
| Capacity (standard unit) | 12V/7Ah/9Ah |
| Typical recharge time) | 6~8 hours (to 90% of full capacity) |
| Charge current | 1A(Standard unit); Long run unit Max.current10A(charge current can be set according to battery capacity installed) |
| SYSTEM FEATURES | |
| Transfer time | Mains to Battery:0ms; Mains to Bypass:0ms |
| Overload / Line Mode | Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately |
| Overload / Bypass Mode | 40A(Breaker) | 60A(Breaker)Follow the catalogue for more information |
| Short circuit | Hold Whole System |
| Overheat | Line Mode: Turn to Bypass; Backup Mode: Shut down UPS immediately |
| Low battery voltage | Alarm and Switch off |
| Self-diagnostics | Upon Power On and Software Control |
| Battery | Advanced Battery Management |
| Audible & Visual alarms | Line Failure, Battery Low, Overload, System Fault |
| LED & LCD display | Line Mode, Bat. Mode, Eco Mode, Bypass Mode, Battery Low, Overload & UPS Fault |
| LCD display | Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage, Inner Temperature & Remaining Battery Backup Time |
| Comunication interface | RS232,USB,SNMP card(optional), Parallel card(optional), Relay card (optional) |
| ENVIRONMENTAL | |
| Operating temperature | 0oC~40oC |
| Storage temperature | -25oC~55oC |
| Humidity range | 0~95% (non-condensing) |
| Altitude | < 1500m |
| Noise level | <55dB |
| PHYSICAL | |
| Dimension D×W×H (mm) | 460x191x720 |
| Net weight (kg) | 54 | 63Follow the catalogue for more information |
| STANDARDS | |
| Safety | IEC/EN62040-1,IEC/EN60950-1 |
| EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
| BATTERY BANK | |
| Model | DPS-BT Series |
| Battery type& Max.quantity | 2×20pcs/7Ah/(9Ah) |
| PHYSICAL OF BATTERY BANK | |
| Dimensions D×W×H (mm) | 597×250×616 |
| Net weight (kg) | 122/134 |