INFINITYPOWER · İSTANBUL, TÜRKİYE+90 212 689 86 84
← DataPower

INFINITYPOWER / MODEL VE PARÇA NUMARASI

DPS-6000

DataPower · BT ve hassas ekipman için online çift çevrim UPS.

Bu model hakkında bilgi alın ↗

Teknik etiketler ve değerler orijinal İngilizce kataloğu izler. “/”, boş değerler ve üretici tutarsızlıkları korunmuştur; nihai model seçimini ekibimizle doğrulayın.

DataPower Series — Technical Specifications

PDF · sayfa 9 ↗
DataPower Series — Technical Specifications
Teknik özellikDPS-6000
General
Capacity (VA/Watts)6k / 5.4k
INPUT
Nominal voltage220/230/240Vac
Operating voltage range120~276Vac
Operating frequency range50Hz:45~55Hz;60Hz:54~66Hz(auto sensing)
Power factor≥0.99
Bypass voltage rangeMax.voltage: 220V: +25%(optional +10%,+15%,+20% ) 230V: +20% (optional +10%,+15%) 240V: +15% (optional +10%) Min.voltage: -45% (optional -20%,-30%)
ECO rangeSame as the bypass
Harmonic distortion (THDi)<3%(100% linear load)
Generator inputSupport
OUTPUT
Rated voltage220/230/240Vac
Power factor0.9
Voltage regulation±1%
Frequency / Line Mode±1%/±2%/±4%/±5%/±10% of the rated frequency(optional)
Frequency / Bat. Mode50/60(±0.1)Hz
Crest factor3:1
Harmonic distortion (THDv)≤2% with linear load ≤5% with non-linear load
Efficiency>95%
BATTERY
Battery voltage±96/108/120Vdc (optional)
Capacity (standard unit)12V/7Ah/9Ah
Typical recharge time)6~8 hours (to 90% of full capacity)
Charge current1A(Standard unit); Long run unit Max.current10A(charge current can be set according to battery capacity installed)
SYSTEM FEATURES
Transfer timeMains to Battery:0ms; Mains to Bypass:0ms
Overload / Line ModeLoad≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, >150% turn to bypass mode immediately
Overload / Bypass Mode40A(Breaker) | 60A(Breaker)Follow the catalogue for more information
Short circuitHold Whole System
OverheatLine Mode: Turn to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltageAlarm and Switch off
Self-diagnosticsUpon Power On and Software Control
BatteryAdvanced Battery Management
Audible & Visual alarmsLine Failure, Battery Low, Overload, System Fault
LED & LCD displayLine Mode, Bat. Mode, Eco Mode, Bypass Mode, Battery Low, Overload & UPS Fault
LCD displayInput Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage, Inner Temperature & Remaining Battery Backup Time
Comunication interfaceRS232,USB,SNMP card(optional), Parallel card(optional), Relay card (optional)
ENVIRONMENTAL
Operating temperature0oC~40oC
Storage temperature-25oC~55oC
Humidity range0~95% (non-condensing)
Altitude< 1500m
Noise level<55dB
PHYSICAL
Dimension D×W×H (mm)460x191x720
Net weight (kg)54 | 63Follow the catalogue for more information
STANDARDS
SafetyIEC/EN62040-1,IEC/EN60950-1
EMCIEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
BATTERY BANK
ModelDPS-BT Series
Battery type& Max.quantity2×20pcs/7Ah/(9Ah)
PHYSICAL OF BATTERY BANK
Dimensions D×W×H (mm)597×250×616
Net weight (kg)122/134