INFINITYPOWER / MODEL VE PARÇA NUMARASI
PEX10-200KVA
PowerExpand · Büyüyen güç ihtiyaçları için modüler UPS mimarisi.
Bu model hakkında bilgi alın ↗Teknik etiketler ve değerler orijinal İngilizce kataloğu izler. “/”, boş değerler ve üretici tutarsızlıkları korunmuştur; nihai model seçimini ekibimizle doğrulayın.
PowerExpand Series — Technical Specifications
PDF · sayfa 29 ↗| Teknik özellik | PEX10-200KVA |
|---|---|
| General | |
| Capacity(VA/Watts) / HPM module | 10k / 9k, 20k / 18k |
| Capacity(VA/Watts) / HPM module | 10k / 9k, 20k / 18k |
| INPUT | |
| Nominal voltage | 380/400/415Vac, (3Ph+N+PE) |
| Operating voltage range | 208~478Vac |
| Operating frequency range | 40~70Hz |
| Power factor | ≥0.99 |
| Bypass voltage range | Max.voltage: 220v +25%(optional +10%,+15%,+20% ) 230v 20% (optional +10%,+15%) 240v 15%(optional +10%) Min. voltage: -45% (optional -20%,-30%) Frequency protection range: ±10% |
| Harmonic distortion (THDi) | 2%(100% nonlinear load) |
| Generator input | Support |
| OUTPUT | |
| Output voltage | 380/400/415Vac, (3Ph+N+PE) |
| Voltage regulation | ±1% |
| Power factor | 0.9 |
| Output frequency | 1.Line Mode: ±1%,±2%,±4%,±5%,±10% of the rated frequency (optional) 2.Battery Mode: (50/60±0.1%)Hz |
| Crest factor | 3:1 |
| Harmonic distortion (THDv) | ≤2% with linear load ≤5% with non linear load |
| Efficiency | 96.5% |
| BATTERY | |
| Battery voltage | ±192\±204\±216\±228\±240Vdc; battery quantity(optional) |
| Charge current / UPS cabinet | 18A (Max) | 30A (Max) | 60A (Max.)Follow the catalogue for more information |
| Charge current / HPM module | 6A (Max.) (charge current can be set according to battery capacity installed) |
| Backup time | Depends on the capacity of external batteries |
| SYSTEM FEATURES | |
| Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms |
| Overload / Bat. Mode | Load≤110%: last 10min,≤125%: last 1min, ≤150%: last 1S,≥150% shut down UPS immediately |
| Overload / Bat. Mode | Load≤110%: last 10min,≤125%: last 1min, ≤150%: last 1S,≥150% shut down UPS immediately |
| Overload / Bypass Mode | Breaker (10kVA: 20A / 20kVA:40A) |
| Short circuit | Hold whole system |
| Nose suppression | Complies with EN62040-2 |
| Communication interface | 1. UPS cabinet : RS232, RS485, Dry Contact, Intelligent slot x 2(SNMP card,Relay card optional) 2. PEX series UPS module: RS232 |
| ENVIRONMENTAL | |
| Operating temperature | 0oC~40oC |
| Storage temperature | -25oC~55oC |
| Humidity range | 0~95% (non-condensing) |
| Altitude | <1500m |
| Noise level | <65dB |
| PHYSICAL | |
| Dimension D×W×H (mm) / HPM module | 443x580x131 (3U) |
| Dimension D×W×H (mm) / HPM module | 443x580x131 (3U) |
| Net weight (kg) / UPS cabinet | 149 | 152 | 290Follow the catalogue for more information |
| Net weight (kg) / UPS cabinet | 10kVA/26; 20kVA/31 |
| STANDARDS | |
| Safety | IEC/EN62040-1,IEC/EN60950-1 |
| EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |