INFINITYPOWER / MODEL VE PARÇA NUMARASI
PEXP50
PowerExpand Plus · Daha büyük kurulumlar için modüler güç altyapısı.
Bu model hakkında bilgi alın ↗Teknik etiketler ve değerler orijinal İngilizce kataloğu izler. “/”, boş değerler ve üretici tutarsızlıkları korunmuştur; nihai model seçimini ekibimizle doğrulayın.
PowerExpand Plus Series — Technical Specifications
PDF · sayfa 31 ↗| Teknik özellik | PEXP50 |
|---|---|
| General | |
| Capacity(VA/Watts) / HPM module | 50 |
| Capacity(VA/Watts) / HPM module | 50 |
| Capacity(VA/Watts) / Max. Number | 4/6/8/10/12/16/20 |
| Max. Parallel Number | 8 |
| INPUT | |
| Nominal voltage | 380/400/415Vac, (3Ph+N+PE) |
| Operating voltage range | 138~305 for 40% load; 305~485 for 100% load |
| Power factor | ≥0.99 |
| Harmonic Distortion (THDi) | ≤3% (100% Linear load) |
| Bypass voltage range | Max. voltage: 220: +25% (Optional+10%, +15%, +20%) 230: +20% (Optional+10%, +15%), 240: +15% (Optional+10%) Min. voltage: -45% (Optional-10%, -15% -20%, -30%) |
| Bypass Frequency Range (Hz) | 50/60±10% |
| OUTPUT | |
| Nominal Voltage (Vac) | 380/400/415 (3Ph+N+PE) |
| Voltage Regulation | ±1% |
| Output Frequency (Hz) | Line mode: Synchronize with input, when the input frequency >±10% (±1%/±2%/±4%/±5% optional), output 50/60 (±0.1z); Bat. mode: (50/60±0.1%) |
| Crest Factor | 3:1 |
| Harmonic Distortion (THDv) | ≤2% with linear load; ≤4% with nonlinear load |
| Overload / Bypass mode | 30oC: 135% for long term; 40oC: 125% for long term; >1000%, 100ms |
| Overload / Bypass mode | 30oC: 135% for long term; 40oC: 125% for long term; >1000%, 100ms |
| EFFICIENCY* | |
| AC Mode | Up to 96% |
| ECO Mode | Up to 99% |
| HECO Mode | Up to 99% |
| BATTERY | |
| Battery Type | VRLA/Li-ion |
| Battery Voltage (Vdc) | 360~600 |
| Charging Current (Max.)(A) | 20 |
| MANAGEMENT | |
| LCD Display | Line voltage, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault |
| Alarm | Line Failure, Battery Low, Overload, System Fault |
| Communication Ports | RS232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card (Optional), SNMP card (Optional), Battery temperature sensor (Optional) |
| SYSTEM FEATURES | |
| Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately |
| Self-diagnostics | Upon Power On and Software Control |
| Generator Input | Support |
| EPO | Shut down UPS immediately |
| ENVIRONMENTAL | |
| Operating Temperature (oC) | 0~40 |
| Storage Temperature (oC) | -25~55 |
| Humidity Range | 0~95% (Non condensing) |
| Altitude (m) | <1000, derating required when >1000 |
| Noise Level (dB) | Not specified |
| PHYSICAL | |
| Dimension WxDxH (mm) / UPS Cabinet (S/F) | 200/300/400kVA: 600×850×2000 500/600kVA: 1200×850×2000 800/1000kVA: 2000×850×2000 |
| Dimension WxDxH (mm) / Power Module | 440×620×130 |
| Weight (kg) / UPS Cabinet | 200kVA: 270; 300kVA: 290; 400kVA: 310; 500kVA: 650; 600kVA: 720; 800kVA: 980; 1000kVA: 1080 |
| Weight (kg) / Power Module | 34 |
| STANDARDS | |
| Safety | IEC/EN 62040-1, IEC/EN 62477-1 |
| EMC | IEC/EN 62040-2 (IEC 61000-2-2, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11) |
| Performance | IEC 62040-3: 2021, EN IEC 62040-3: 2021 |