INFINITYPOWER / UPS
MegaPower+
10–500 kVA
A broad capacity portfolio for larger protected loads.
Request a quote ↗Original catalogue ↗
Models & part numbers
14 catalogue models. Select a model for its own specification table.
Technical labels and values follow the original English catalogue. “/”, blanks and manufacturer inconsistencies are preserved; confirm final model selection with our team.
MegaPower+ Series — Technical Specifications
PDF · page 25 ↗| Specification | MPPS10K | MPPS15K | MPPS20K | MPPS30K | MPPS40K | MPPS60K | MPPS80K |
|---|---|---|---|---|---|---|---|
| General | |||||||
| Capacity (VA/Watts) | 10k / 8k | 15k / 12k | 20k / 16k | 30k / 24k | 40k / 32k | 60k / 48k | 80k / 64k |
| INPUT | |||||||
| Nominal voltage | 380/400/415Vac, (3Ph+N+PE) | 380/400/415Vac, (3Ph+N+PE) | 380/400/415Vac, (3Ph+N+PE) | 380/400/415Vac, (3Ph+N+PE) | 380/400/415Vac, (3Ph+N+PE) | 380/400/415Vac, (3Ph+N+PE) | 380/400/415Vac, (3Ph+N+PE) |
| Operating voltage range | 208~478Vac | 208~478Vac | 208~478Vac | 208~478Vac | 208~478Vac | 208~478Vac | 208~478Vac |
| Operating frequency range | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz |
| Power factor | ≥0.99 | ≥0.99 | ≥0.99 | ≥0.99 | ≥0.99 | ≥0.99 | ≥0.99 |
| Harmonic distortion (THDI) | 2%(100% nonlinear load) | 2%(100% nonlinear load) | 2%(100% nonlinear load) | 2%(100% nonlinear load) | 2%(100% nonlinear load) | 2%(100% nonlinear load) | 2%(100% nonlinear load) |
| Bypass voltage range | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% |
| Generator input | Support | Support | Support | Support | Support | Support | Support |
| OUTPUT | |||||||
| Output voltage | 380/400/415Vac (3Ph+N+PE) | 380/400/415Vac (3Ph+N+PE) | 380/400/415Vac (3Ph+N+PE) | 380/400/415Vac (3Ph+N+PE) | 380/400/415Vac (3Ph+N+PE) | 380/400/415Vac (3Ph+N+PE) | 380/400/415Vac (3Ph+N+PE) |
| voltage regulation | ±2% | ±2% | ±2% | ±2% | ±2% | ±2% | ±2% |
| Power factor | 0.8%/0.9(Customized) | 0.8%/0.9(Customized) | 0.8%/0.9(Customized) | 0.8%/0.9(Customized) | 0.8%/0.9(Customized) | 0.8%/0.9(Customized) | 0.8%/0.9(Customized) |
| Output frequency | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz |
| Crest frequency | 3:1 | 3:1 | 3:1 | 3:1 | 3:1 | 3:1 | 3:1 |
| Harmonic distortion (THD) | ≤2% with linear load ≤5% with non linear load | ≤2% with linear load ≤5% with non linear load | ≤2% with linear load ≤5% with non linear load | ≤2% with linear load ≤5% with non linear load | ≤2% with linear load ≤5% with non linear load | ≤2% with linear load ≤5% with non linear load | ≤2% with linear load ≤5% with non linear load |
| Efficiency | 94.5% | 95%Follow the catalogue for more information | ||||||
| BATTERY | |||||||
| Battery voltage | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc |
| Battery type | 12V/38Ah (Standard unit) | 12V/38Ah (Standard unit) | 12V/38Ah (Standard unit) | 12V/38Ah (Standard unit) | 12V/38Ah (Standard unit) | 12V/38Ah (Standard unit) | 12V/38Ah (Standard unit) |
| Charge Current (A) (charge current can be set according to battery capacity installed) | 5.7A (Max./Standard unit) 6.0A (Max./Long run unit) | 12A (Max.) | 18A (Max.)Follow the catalogue for more information | ||||||
| SYSTEM FEATURES | |||||||
| Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms | Utility to Battery : 0ms; Utility to bypass: 0ms | Utility to Battery : 0ms; Utility to bypass: 0ms | Utility to Battery : 0ms; Utility to bypass: 0ms | Utility to Battery : 0ms; Utility to bypass: 0ms | Utility to Battery : 0ms; Utility to bypass: 0ms | Utility to Battery : 0ms; Utility to bypass: 0ms |
| Overload / Bat. Mode | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately |
| Overload / Bat. Mode | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately |
| Short circuit | Hold Whole Syetem | Hold Whole Syetem | Hold Whole Syetem | Hold Whole Syetem | Hold Whole Syetem | Hold Whole Syetem | Hold Whole Syetem |
| Overheat | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately |
| Low battery voltage | Alarm and switch off | Alarm and switch off | Alarm and switch off | Alarm and switch off | Alarm and switch off | Alarm and switch off | Alarm and switch off |
| Self-diagnostics | Upon power on and software Control | Upon power on and software Control | Upon power on and software Control | Upon power on and software Control | Upon power on and software Control | Upon power on and software Control | Upon power on and software Control |
| EPO (optional) | Shut down UPS immediately | Shut down UPS immediately | Shut down UPS immediately | Shut down UPS immediately | Shut down UPS immediately | Shut down UPS immediately | Shut down UPS immediately |
| Battery | Advanced Battery Management | Advanced Battery Management | Advanced Battery Management | Advanced Battery Management | Advanced Battery Management | Advanced Battery Management | Advanced Battery Management |
| Nose Suppression | Complies with EN62040-2 | Complies with EN62040-2 | Complies with EN62040-2 | Complies with EN62040-2 | Complies with EN62040-2 | Complies with EN62040-2 | Complies with EN62040-2 |
| Audible& Visual | Line Failure, Battery low, Overload, System Fault | Line Failure, Battery low, Overload, System Fault | Line Failure, Battery low, Overload, System Fault | Line Failure, Battery low, Overload, System Fault | Line Failure, Battery low, Overload, System Fault | Line Failure, Battery low, Overload, System Fault | Line Failure, Battery low, Overload, System Fault |
| Status LED & LCD display | Line mode, Bypass Mode, Battery low, overload, System Fault | Line mode, Bypass Mode, Battery low, overload, System Fault | Line mode, Bypass Mode, Battery low, overload, System Fault | Line mode, Bypass Mode, Battery low, overload, System Fault | Line mode, Bypass Mode, Battery low, overload, System Fault | Line mode, Bypass Mode, Battery low, overload, System Fault | Line mode, Bypass Mode, Battery low, overload, System Fault |
| Reading on the LCD display Communication interface | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) |
| ENVIRONMENTAL | |||||||
| Operating temperature | 0~40 oC | 0~40 oC | 0~40 oC | 0~40 oC | 0~40 oC | 0~40 oC | 0~40 oC |
| Storage temperature | -25~55oC | -25~55oC | -25~55oC | -25~55oC | -25~55oC | -25~55oC | -25~55oC |
| Humidity range Altitude | 0~95% (Non condensing) <1500m | 0~95% (Non condensing) <1500m | 0~95% (Non condensing) <1500m | 0~95% (Non condensing) <1500m | 0~95% (Non condensing) <1500m | 0~95% (Non condensing) <1500m | 0~95% (Non condensing) <1500m |
| Noise level | <55dB | <55dB | <55dB | <55dB | <55dB | <55dB | <55dB |
| PHYSICAL | |||||||
| Dimension D×W×H (mm) | 780x600x1200 | 780x600x1200 | 780x600x1200 | 780x600x1200 | 780x600x1200 | 780x600x1200 | 780x600x1200 |
| Net weight (kg) | S:591 H:123 | S:594 H:126 | S:595 H:127 | 158 | 195Follow the catalogue for more information | ||||||
| STANDARDS | |||||||
| Safety | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 |
| EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
MegaPower+ Series — Technical Specifications
PDF · page 26 ↗| Specification | MPPS110K | MPPS120K | MPPS160K | MPPS200K | MPPS300K | MPPS400K | MPPS500K |
|---|---|---|---|---|---|---|---|
| General | |||||||
| Capacity (VA/Watts) | 100k / 80k | 120k / 96k | 160k / 128k | 200k / 160k | 300k / 240k | 400k / 320k | 500k / 400k |
| INPUT | |||||||
| Nominal voltage | 380/400/415Vac, (3Ph+N+PE) | 380/400/415Vac, (3Ph+N+PE) | 380/400/415Vac, (3Ph+N+PE) | 380/400/415Vac, (3Ph+N+PE) | 380/400/415Vac, (3Ph+N+PE) | 380/400/415Vac, (3Ph+N+PE) | 380/400/415Vac, (3Ph+N+PE) |
| Operating voltage range | 208~478Vac | 208~478Vac | 208~478Vac | 208~478Vac | 208~478Vac | 208~478Vac | 208~478Vac |
| Operating frequency range | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz | 40~70Hz |
| Power factor | ≥0.99 | ≥0.99 | ≥0.99 | ≥0.99 | ≥0.99 | ≥0.99 | ≥0.99 |
| Harmonic distortion (THDI) | 3%(100% nonlinear load) | 3%(100% nonlinear load) | 3%(100% nonlinear load) | 3%(100% nonlinear load) | 3%(100% nonlinear load) | 3%(100% nonlinear load) | 3%(100% nonlinear load) |
| Bypass voltage range | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% |
| Generator input | Support | Support | Support | Support | Support | Support | Support |
| OUTPUT | |||||||
| Output voltage | 380/400/415Vac (3Ph+N+PE) | 380/400/415Vac (3Ph+N+PE) | 380/400/415Vac (3Ph+N+PE) | 380/400/415Vac (3Ph+N+PE) | 380/400/415Vac (3Ph+N+PE) | 380/400/415Vac (3Ph+N+PE) | 380/400/415Vac (3Ph+N+PE) |
| voltage regulation | ±1% | ±1% | ±1% | ±1% | ±1% | ±1% | ±1% |
| Power factor | 0.8%/0.9(Customized) | 0.8%/0.9(Customized) | 0.8%/0.9(Customized) | 0.8%/0.9(Customized) | 0.8%/0.9(Customized) | 0.8%/0.9(Customized) | 0.8%/0.9(Customized) |
| Output frequency | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz |
| Crest frequency | 3:1 | 3:1 | 3:1 | 3:1 | 3:1 | 3:1 | 3:1 |
| Harmonic distortion (THD) | ≤2% with linear load ≤5% with non linear load | ≤2% with linear load ≤5% with non linear load | ≤2% with linear load ≤5% with non linear load | ≤2% with linear load ≤5% with non linear load | ≤2% with linear load ≤5% with non linear load | ≤2% with linear load ≤5% with non linear load | ≤2% with linear load ≤5% with non linear load |
| Efficiency | 94.5% | 95%Follow the catalogue for more information | ||||||
| BATTERY | |||||||
| Battery voltage | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc |
| Charge Current (A) (charge current can be set according to battery capacity installed) | 24A(MAX) | 36A(MAX) | 50A(MAX) | 80A(MAX) | 100A(MAX) | 130A(MAX)Follow the catalogue for more information | ||||||
| SYSTEM FEATURES | |||||||
| Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms | Utility to Battery : 0ms; Utility to bypass: 0ms | Utility to Battery : 0ms; Utility to bypass: 0ms | Utility to Battery : 0ms; Utility to bypass: 0ms | Utility to Battery : 0ms; Utility to bypass: 0ms | Utility to Battery : 0ms; Utility to bypass: 0ms | Utility to Battery : 0ms; Utility to bypass: 0ms |
| Overload / Bat. Mode | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately |
| Overload / Bat. Mode | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately |
| Short circuit | Hold Whole Syetem | Hold Whole Syetem | Hold Whole Syetem | Hold Whole Syetem | Hold Whole Syetem | Hold Whole Syetem | Hold Whole Syetem |
| Overheat | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately |
| Low battery voltage | Alarm and switch off | Alarm and switch off | Alarm and switch off | Alarm and switch off | Alarm and switch off | Alarm and switch off | Alarm and switch off |
| Self-diagnostics | Upon power on and software Control | Upon power on and software Control | Upon power on and software Control | Upon power on and software Control | Upon power on and software Control | Upon power on and software Control | Upon power on and software Control |
| EPO (optional) | Shut down UPS immediately | Shut down UPS immediately | Shut down UPS immediately | Shut down UPS immediately | Shut down UPS immediately | Shut down UPS immediately | Shut down UPS immediately |
| Battery | Advanced Battery Management | Advanced Battery Management | Advanced Battery Management | Advanced Battery Management | Advanced Battery Management | Advanced Battery Management | Advanced Battery Management |
| Nose Suppression | Complies with EN62040-2 | Complies with EN62040-2 | Complies with EN62040-2 | Complies with EN62040-2 | Complies with EN62040-2 | Complies with EN62040-2 | Complies with EN62040-2 |
| Audible& Visual | Line Failure, Battery low, Overload, System Fault | Line Failure, Battery low, Overload, System Fault | Line Failure, Battery low, Overload, System Fault | Line Failure, Battery low, Overload, System Fault | Line Failure, Battery low, Overload, System Fault | Line Failure, Battery low, Overload, System Fault | Line Failure, Battery low, Overload, System Fault |
| Status LED & LCD display | Line mode, Bypass Mode, Battery low, Battery bad, overload &UPS Fault | Line mode, Bypass Mode, Battery low, Battery bad, overload &UPS Fault | Line mode, Bypass Mode, Battery low, Battery bad, overload &UPS Fault | Line mode, Bypass Mode, Battery low, Battery bad, overload &UPS Fault | Line mode, Bypass Mode, Battery low, Battery bad, overload &UPS Fault | Line mode, Bypass Mode, Battery low, Battery bad, overload &UPS Fault | Line mode, Bypass Mode, Battery low, Battery bad, overload &UPS Fault |
| Reading on the LCD display Communication interface | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) |
| ENVIRONMENTAL | |||||||
| Operating temperature | 0~40 oC | 0~40 oC | 0~40 oC | 0~40 oC | 0~40 oC | 0~40 oC | 0~40 oC |
| Storage temperature | -25~55oC | -25~55oC | -25~55oC | -25~55oC | -25~55oC | -25~55oC | -25~55oC |
| Humidity range | 0~95% (Non condensing) | 0~95% (Non condensing) | 0~95% (Non condensing) | 0~95% (Non condensing) | 0~95% (Non condensing) | 0~95% (Non condensing) | 0~95% (Non condensing) |
| Altitude | <1500m | <1500m | <1500m | <1500m | <1500m | <1500m | <1500m |
| Noise level | 70dB | 73dBFollow the catalogue for more information | ||||||
| PHYSICAL | |||||||
| Dimension D×W×H (mm) | 780x600x1600 | 850x600x1600 | 850x600x2000 | 850x1200x2000Follow the catalogue for more information | ||||||
| Net weight (kg) | 286 | 288 | 348 | 380 | 600 | 815 | 860Follow the catalogue for more information | ||||||
| STANDARDS | |||||||
| Safety | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 | IEC/EN62040-1,IEC/EN60950-1 |
| EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |
Catalogue features and options · PDF 24
Mega Power + Series
--------------------------------------
ONLINE DOUBLE CONVERSION UPS
10kVA To 500kVA (0.8 PF)
Three Phase input/output (3:3)
Features • Megatec/Mod Bus protocol supported
• Powerful chrager built in
• DSP-controlled technology
• Versatile communication interfaces provided for
• Parallel redundacy up to 4 units
different applications
• Wide input voltage and frequency
• Superior overload capability
windows
• Programmable control and monitoring software
• Easy-to-operate LCD display
• High power density up to 500kVA for
space saving
• Unity power factor and low input
distortion
• Output power factor at 0.8(0.9 optional)
• ECO mode for energy saving
• Common or seperate battery
• Programmable battery voltage from+-
192Vdc to +- 240Vdc
• Intelligent charge modes with smart
charge current adjustment
Control Panel
24
--------------------------------------
ONLINE DOUBLE CONVERSION UPS
10kVA To 500kVA (0.8 PF)
Three Phase input/output (3:3)
Features • Megatec/Mod Bus protocol supported
• Powerful chrager built in
• DSP-controlled technology
• Versatile communication interfaces provided for
• Parallel redundacy up to 4 units
different applications
• Wide input voltage and frequency
• Superior overload capability
windows
• Programmable control and monitoring software
• Easy-to-operate LCD display
• High power density up to 500kVA for
space saving
• Unity power factor and low input
distortion
• Output power factor at 0.8(0.9 optional)
• ECO mode for energy saving
• Common or seperate battery
• Programmable battery voltage from+-
192Vdc to +- 240Vdc
• Intelligent charge modes with smart
charge current adjustment
Control Panel
24