INFINITYPOWER / MODEL & PART NUMBER
MPPS200K
MegaPower+ · A broad capacity portfolio for larger protected loads.
Enquire about this model ↗Technical labels and values follow the original English catalogue. “/”, blanks and manufacturer inconsistencies are preserved; confirm final model selection with our team.
MegaPower+ Series — Technical Specifications
PDF · page 26 ↗| Specification | MPPS200K |
|---|---|
| General | |
| Capacity (VA/Watts) | 200k / 160k |
| INPUT | |
| Nominal voltage | 380/400/415Vac, (3Ph+N+PE) |
| Operating voltage range | 208~478Vac |
| Operating frequency range | 40~70Hz |
| Power factor | ≥0.99 |
| Harmonic distortion (THDI) | 3%(100% nonlinear load) |
| Bypass voltage range | Max.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10% |
| Generator input | Support |
| OUTPUT | |
| Output voltage | 380/400/415Vac (3Ph+N+PE) |
| voltage regulation | ±1% |
| Power factor | 0.8%/0.9(Customized) |
| Output frequency | 1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz |
| Crest frequency | 3:1 |
| Harmonic distortion (THD) | ≤2% with linear load ≤5% with non linear load |
| Efficiency | 94.5% | 95%Follow the catalogue for more information |
| BATTERY | |
| Battery voltage | Standard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc |
| Charge Current (A) (charge current can be set according to battery capacity installed) | 24A(MAX) | 36A(MAX) | 50A(MAX) | 80A(MAX) | 100A(MAX) | 130A(MAX)Follow the catalogue for more information |
| SYSTEM FEATURES | |
| Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms |
| Overload / Bat. Mode | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately |
| Overload / Bat. Mode | Load≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately |
| Short circuit | Hold Whole Syetem |
| Overheat | Line mode: Switch to Bypass; Backup Mode: shut down UPS immediately |
| Low battery voltage | Alarm and switch off |
| Self-diagnostics | Upon power on and software Control |
| EPO (optional) | Shut down UPS immediately |
| Battery | Advanced Battery Management |
| Nose Suppression | Complies with EN62040-2 |
| Audible& Visual | Line Failure, Battery low, Overload, System Fault |
| Status LED & LCD display | Line mode, Bypass Mode, Battery low, Battery bad, overload &UPS Fault |
| Reading on the LCD display Communication interface | input Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional) |
| ENVIRONMENTAL | |
| Operating temperature | 0~40 oC |
| Storage temperature | -25~55oC |
| Humidity range | 0~95% (Non condensing) |
| Altitude | <1500m |
| Noise level | 70dB | 73dBFollow the catalogue for more information |
| PHYSICAL | |
| Dimension D×W×H (mm) | 780x600x1600 | 850x600x1600 | 850x600x2000 | 850x1200x2000Follow the catalogue for more information |
| Net weight (kg) | 286 | 288 | 348 | 380 | 600 | 815 | 860Follow the catalogue for more information |
| STANDARDS | |
| Safety | IEC/EN62040-1,IEC/EN60950-1 |
| EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |