INFINITYPOWER · İSTANBUL, TÜRKİYE+90 212 689 86 84
← MegaPower+

INFINITYPOWER / MODEL & PART NUMBER

MPPS300K

MegaPower+ · A broad capacity portfolio for larger protected loads.

Enquire about this model ↗

Technical labels and values follow the original English catalogue. “/”, blanks and manufacturer inconsistencies are preserved; confirm final model selection with our team.

MegaPower+ Series — Technical Specifications

PDF · page 26 ↗
MegaPower+ Series — Technical Specifications
SpecificationMPPS300K
General
Capacity (VA/Watts)300k / 240k
INPUT
Nominal voltage380/400/415Vac, (3Ph+N+PE)
Operating voltage range208~478Vac
Operating frequency range40~70Hz
Power factor≥0.99
Harmonic distortion (THDI)3%(100% nonlinear load)
Bypass voltage rangeMax.voltage: 220v + 25%(optional+10%,+15%,+20%) 230v 20% (optional + 10%,+15%) 240v 15%(optional + 10%) Min. Voltage: -45% (optional - 20%, -30%) Frequency protection range: ±10%
Generator inputSupport
OUTPUT
Output voltage380/400/415Vac (3Ph+N+PE)
voltage regulation±1%
Power factor0.8%/0.9(Customized)
Output frequency1.line mode: ±1%/ ±2%/ ±4%/ ±5%/ ±10% of the rated frequency(optional) 2. Battery Mode: (50/60 ±0.2%)Hz
Crest frequency3:1
Harmonic distortion (THD)≤2% with linear load ≤5% with non linear load
Efficiency94.5% | 95%Follow the catalogue for more information
BATTERY
Battery voltageStandard unit: ±216Vdc; Long run unit optional Voltage: ±192V/ ±204V/ ±216V/ ±228V/ ±240Vdc
Charge Current (A) (charge current can be set according to battery capacity installed)24A(MAX) | 36A(MAX) | 50A(MAX) | 80A(MAX) | 100A(MAX) | 130A(MAX)Follow the catalogue for more information
SYSTEM FEATURES
Transfer timeUtility to Battery : 0ms; Utility to bypass: 0ms
Overload / Bat. ModeLoad≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately
Overload / Bat. ModeLoad≤110%: last 10min,≤125%: last 1min,≤150%: last 5S,≥150% shut down UPS immediately
Short circuitHold Whole Syetem
OverheatLine mode: Switch to Bypass; Backup Mode: shut down UPS immediately
Low battery voltageAlarm and switch off
Self-diagnosticsUpon power on and software Control
EPO (optional)Shut down UPS immediately
BatteryAdvanced Battery Management
Nose SuppressionComplies with EN62040-2
Audible& VisualLine Failure, Battery low, Overload, System Fault
Status LED & LCD displayLine mode, Bypass Mode, Battery low, Battery bad, overload &UPS Fault
Reading on the LCD display Communication interfaceinput Voltage, input Frequency, output Voltage, output Frequency, load Percentage, Battery Voltage& inner Temperature RS232, RS485, Parallel, Intelligent slot, Relay card(optional), SNMP card(optional)
ENVIRONMENTAL
Operating temperature0~40 oC
Storage temperature-25~55oC
Humidity range0~95% (Non condensing)
Altitude<1500m
Noise level70dB | 73dBFollow the catalogue for more information
PHYSICAL
Dimension D×W×H (mm)780x600x1600 | 850x600x1600 | 850x600x2000 | 850x1200x2000Follow the catalogue for more information
Net weight (kg)286 | 288 | 348 | 380 | 600 | 815 | 860Follow the catalogue for more information
STANDARDS
SafetyIEC/EN62040-1,IEC/EN60950-1
EMCIEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8