INFINITYPOWER / MODEL VE PARÇA NUMARASI
DPPS-10K1-1
DataPower+ · Farklı giriş yapılandırmalarıyla esnek online güç koruması.
Bu model hakkında bilgi alın ↗Teknik etiketler ve değerler orijinal İngilizce kataloğu izler. “/”, boş değerler ve üretici tutarsızlıkları korunmuştur; nihai model seçimini ekibimizle doğrulayın.
DataPower+ Series — Technical Specifications
PDF · sayfa 15 ↗| Teknik özellik | DPPS-10K1-1 |
|---|---|
| General | |
| Capacity(VA/Watts) | 10k / 9k |
| INPUT | |
| Nominal Voltage | 220/230/240Vac(L+N+PE) |
| Operating voltage range | 110~300 (110~300@50% load/176~300@100% load) |
| Operating frequency range | 45~55Hz/54~66Hz±0.5Hz |
| Power factor | ≥0.99 |
| Bypass voltage range | 220V: +25%(optional +10%,+15%,+20% ) 230: +20% (optional +10%,+15%) 240: +15% (optional +10%) Min. voltage: -45% (optional -20%,-30%) |
| ECO range | Same as bypass |
| Harmonic distortion (THDi) | ≤3%(100% linear load) |
| Generator input | Support |
| OUTPUT | |
| Output voltage | 220/230/240Vac |
| Power factor | 0.9 |
| Voltage regulation | ±2% |
| Frequency / Bat. Mode | 50/60 (±0.1)Hz |
| Frequency / Bat. Mode | 50/60 (±0.1)Hz |
| Crest factor | 3:1 |
| Harmonic distortion (THDv) | ≤2% with linear load ≤5% with non linear load |
| Waveform | Pure Sinewave |
| Efficiency | >95% |
| BATTERY | |
| Battery voltage | Optional Voltage: ±96/±108/±120Vdc VRLA or LI-ion |
| Typical recharge time | 6~8 hours (to 90% of full capacity) |
| Charge current | Maximum Current 6A; charge current can be set according to battery capacity installed. |
| SYSTEM FEATURES | |
| Transfer time | Utility to Battery : 0ms; Utility to bypass: 0ms |
| Overload / Line Mode | Load≤110%: last 60min; ≤125%: last 10min; ≤150%: last 1S;>150% turn to bypass mode |
| Overload / Bypass Mode | 60A(Input breaker) |
| Short Circuit | Hold Whole System |
| Overheat | Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately |
| Low battery voltage | Alarm and Switch off |
| Self-diagnostics | Upon Power On and Software Control |
| EPO (optional) | Shut down UPS immediately |
| Battery | Advanced Battery Management |
| Noise Suppression | Complies with EN62040-2 |
| Audible & Visual alarms | Line Failure, Battery Low, Overload, System Fault |
| Status LED & LCD display | Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault |
| Reading on the LCD display | Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage, Inner Temperature & Remaining Battery Backup Time |
| Comunication interface | USB,RS232,Parallel Port, SNMPcard/Relay card (optional) |
| ENVIRONMENTAL | |
| Operating temperature | 0~40oC |
| Storage temperature | -25~55oC |
| Humidity range | 0~95% (non condensing) |
| Altitude | <1500m |
| Noise level | <50 |
| PHYSICAL | |
| Dimension W×H×D (mm) | 440×621.5×86.5 (2U) | 440×621.5×175 (4U)Follow the catalogue for more information |
| Net Weight (kg) | 15 | 57/65 | 17 | 67Follow the catalogue for more information |
| STANDARDS | |
| Safety | IEC/EN62040-1,IEC/EN60950-1 |
| EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |