INFINITYPOWER / MODEL VE PARÇA NUMARASI
DPPS-1500
DataPower+ · Farklı giriş yapılandırmalarıyla esnek online güç koruması.
Bu model hakkında bilgi alın ↗Teknik etiketler ve değerler orijinal İngilizce kataloğu izler. “/”, boş değerler ve üretici tutarsızlıkları korunmuştur; nihai model seçimini ekibimizle doğrulayın.
DataPower+ Series — Technical Specifications
PDF · sayfa 13 ↗| Teknik özellik | DPPS-1500 |
|---|---|
| General | |
| Capacity (VA/Watts) | 1500/1350 |
| INPUT | |
| Rated Voltage | 200/208/220/230/240Vac |
| Voltage Range | 110~290Vac |
| Frequency Range | 45~65Hz(auto-detect) |
| Power Factor | ≥0.98 |
| Bypass Voltage Range | Max.voltage: +15%(optional +5%,+10%,+25% ) Min. voltage: -45% (optional-15% -20%,-30%) Frequency protection range: ±10% |
| Generator Input | Support |
| OUTPUT | |
| Rated Voltage | 200/208/220/230/240Vac |
| Power Factor | 0.9 |
| Voltage Regulation | ±2% |
| Frequency / Utility Mode | 50Hz or 60Hz(Synchronized to Mains) |
| Frequency / Battery Mode | 50/60Hz±0.02Hz |
| Crest Factor | 3:1 |
| THDv | ≤3% with linear load ≤5% with non linear load |
| Efficiency / Battery Mode(full load) | >90% |
| Efficiency / Battery Mode(full load) | >90% |
| Efficiency / ECO Mode(full load) | >99% |
| BATTERY | |
| Standard Model / Typical Recharge Time | 4 hours recover to 90% capacity |
| Standard Model / Numbers | 2 | 3 | 4 | 6Follow the catalogue for more information |
| Standard Model / Typical Recharge Time | 4 hours recover to 90% capacity |
| Standard Model / Charging Current(max.) | 1.4A |
| Standard Model / Charging Voltage | 27.4Vdc±1% | 41.0Vdc±1% | 54.7Vdc±1% | 82.1Vdc±1%Follow the catalogue for more information |
| Long-run Model / Charging Current(max.) | 6A/12A(double board) | 7A/14A(double board)Follow the catalogue for more information |
| Long-run Model / Charging Current(max.) | 6A/12A(double board) | 7A/14A(double board)Follow the catalogue for more information |
| Long-run Model / Charging Voltage | 27.4Vdc±1% | 41.0Vdc±1% | 54.7Vdc±1% | 82.1Vdc±1%Follow the catalogue for more information |
| SYSTEM FEATURES | |
| Transfer time | Utility to Battery : 0ms; Utility to bypass< 4ms |
| Overload / Bat. Mode | Load <100%~150%: 30S; Load > 150%: 300ms then shut down UPS completely |
| Overload / Bat. Mode | Load <100%~150%: 30S; Load > 150%: 300ms then shut down UPS completely |
| Overload / Bypass Mode | Load > 130%: 60S then shut down output |
| Audible & Visual | Line Failure, Battery Low, Overload, System Fault |
| Status LED & LCD | Load/Battery/Input/Output/Operating Mode Information |
| ENVIRONMENTAL | |
| Dimension(W×H×D)mm | 440×86.5×430 | 440×86.5×572 | 440×86.5×696Follow the catalogue for more information |
| Weight (Kg) | 15.1 | 18.1 | 22.2 | 25.5Follow the catalogue for more information |
| Input Connection | IEC320 C14-10A | IEC320 C20-16A | IEC320-C20-16AFollow the catalogue for more information |
| Output Connection | IEC320 C13-10A x 6 | IEC320 C13-10A x 6 &C19-16A x 1Follow the catalogue for more information |
| Communication Interface | Smart RS232/USB Port/RJ45/SNMP Card (independent to RS232) |
| Operating Temperature | 0~40oC |
| Storage Temperature | -25~+55oC |
| Humidity | 0~90% (non condensing) |
| Altitude | <1500m.(derating while > 1500m) |
| Noise | <50dB(at 1 meter) |
| BATTERY BANK | |
| Model | DPPS-BR04009 | DPPS-BR06009 | DPPS-BR08009 | DPPS-BR12009Follow the catalogue for more information |
| Bat.Type&Max.Quantity | 9AH×4 | 9AH×6 | 9AH×8 | 9AH×12Follow the catalogue for more information |
| PHYSICAL OF BATTERY BANK | |
| Unit Dimensions W×H×D (mm) | 440×86.5×430 | 440×86.5×572 | 440×86.5×696Follow the catalogue for more information |
| Weight (Kg) | 12 | 15 | 22 | 32Follow the catalogue for more information |