INFINITYPOWER · İSTANBUL, TÜRKİYE+90 212 689 86 84
← DataPower+

INFINITYPOWER / MODEL VE PARÇA NUMARASI

DPPS-6K3-1

DataPower+ · Farklı giriş yapılandırmalarıyla esnek online güç koruması.

Bu model hakkında bilgi alın ↗

Teknik etiketler ve değerler orijinal İngilizce kataloğu izler. “/”, boş değerler ve üretici tutarsızlıkları korunmuştur; nihai model seçimini ekibimizle doğrulayın.

DataPower+ Series — Technical Specifications

PDF · sayfa 17 ↗
DataPower+ Series — Technical Specifications
Teknik özellikDPPS-6K3-1
General
Capacity(VA/Watts)6k / 5.4k
INPUT
Nominal Voltage380/400/415Vac(3Ph+N+PE) or 220/230/240Vac(L+N+PE)
Operating voltage range208~478Vac or 120Vac~276Vac
Operating frequency range50Hz:45~55Hz;60Hz:54~66Hz(auto sensing)
Power factor≥0.99
Bypass voltage rangeMax. voltage: 220V: +25%(optional +10%,+15%,+20% ) 230V: +20% (optional +10%,+15%), 240V: +15% (optional +10%) Min. voltage: -45% (optional -20%,-30%)
Bypass frequency rangeFrequency protection range:±10
ECO rangeSame as bypass
Harmonic distortion (THDi)≤5%(100% linear load)
Generator inputSupport
OUTPUT
Output voltage220/230/240Vac
Power factor0.9
Voltage regulation±1%
Frequency / Bat. Mode50/60(±0.1)Hz
Frequency / Bat. Mode50/60(±0.1)Hz
Crest factor3:1
Harmonic distortion (THDv)≤2% with linear load, ≤5% with non linear load
Efficiency>95%
BATTERY
Battery voltage±96/108/120Vdc (optional)
Backup timeLong run unit depends on the capacity of external batteries Estimated remaining time displayed on the LCD
Typical recharge time6~8 hours (to 90% of full capacity)
Charge currentMaximum Current 10A; charge current can be set according to battery capacity installed
SYSTEM FEATURES
Transfer timeMains to Battery:0ms; Mains to Bypass:0ms
Overload / Line ModeLoad≤110%:60min; ≤125%:last 10min; ≤150%:last 1min;>150% turn to bypass mode
Overload / Bypass Mode40A(Input breaker)
Short CircuitHold Whole System
OverheatLine Mode: Turn to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltageAlarm and Switch off
Self-diagnosticsUpon Power On and Software Control
BatteryAdvanced Battery Management
Audible & Visual alarmsLine Failure, Battery Low, Overload, System Fault
Status LED & LCD displayLine Mode, Bat. Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault
Reading on the LCD displayInput Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage, Inner Temperature & Remaining Battery Backup Time
Comunication interfaceRS232,USB,SNMP card(optional), Relay card (optional)
ENVIRONMENTAL
Operating temperature0oC~40oC
Storage temperature-25oC~55oC
Humidity range0~95% (non condensing)
Altitude<1500m
Noise level<55dB
PHYSICAL
Dimension W×H×D (mm)580×443×131(3U)
Net Weight (kg)23
STANDARDS
SafetyIEC/EN62040-1,IEC/EN60950-1
EMCIEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
BATTERY BANK
ModelDPPS-BR Series
Battery type& Max.quantity7Ah×20
PHYSICAL OF BATTERY BANK
Dimensions D×W×H (mm)720×443×131(3U)